Rack Monitoring System Advanced
Monitor and control all relevant functions and environmental conditions in your server room or elsewhere automatically and remotely!
A wide range of sensors allow for measurement of environmental values and for computerized automated reactions and for sending alarms.
In comparison to the Rack Monitoring System LITE the model Advanced uses more memory and a faster processor and offers an extended range of features:
- Email function in case of alarm
- Integrated DHCP server
- Integrated time server
- Optional local control via front panel push buttons
- Optional local status review via front panel display
- 40 instead of only 12 programmable filter rules
- 100 instead of only 12 user accounts with individual rights
- Control of all 3 phases of the power
- Increased number of measurement and switched IN/OUTPUTS
- UPS interface
FEATURES & SPECIFICATIONS
The Rack Monitoring System can always reacts automatically on changes of environmental conditions with pre programmed reactions. In addition alarms can be set via alarm bell, display, switched outputs and SNMP network management and/or email. The RMS can be integrated into any SNMP software (i.e. HP Open View, Novell ManageWise, other SNMP-Shareware, etc.).
The RMS can be remotely accessed by up toi 100 different users individually password protected.
Permanent managemnt of:
- Fans
- Heating system / air condition
- RS-232 devices, i.e. remote switchanble power outlets
Remote accessand configuration via terminal or network:
- LAN (SMNP, Telnet, ...)
- Management console
- Browser
Permanent control of:
- Temperature
- Humidity
- Firr / Smoke
- Door contacts
- Vibration / Earth quake
- Power
Accessories and sensors:
- Temperatue sensor No. 32420
- Temperature sensor LITE (NTC resistor) No. 32434
- Humidity sensor No. 32421
- Combo sensor Temperature & Humidity No. 32422
- Smoke sensor with German VdS approval No. 32423
- Smoke sensor without approval No. 32435
- Door contact sensor No. 32424
- Water flood sensor (only for RMS Advanced) No. 32437
- Vibration sensor (only for RMS Advanced) No. 32426
- Infrared motion sensor No. 32427
- RS-232 remote switchable power outlet COMPower Switch LITE 4 No. 32452
- RS-232 remote switchable power outlet COMPower Switch LITE 8 No. 32453
- Extension cable Sensor T & F 5m No. 32428
- Extension cable Sensor T & F 10m No. 32429
- Extension cable Sensor T & F 15m No. 32430
- Extension cable Sensor T & F 20m No. 32431
Model | RMS LITE (No. 32419) | RMS ADVANCED (No. 32418) |
Processor, Memory RAM/Flash | 25MHz, 4/8 MB | 33MHz, 16/32 MB |
Housing, Dimensions (WxHxD, mm) | 19"1U, 484(445)x44x230 | 19"1U, 484(445)x44x230 |
Weight approx.: net./incl. packaging | 3,2 / 4,1kg | 3,6 / 5,1kg |
Power requirement | 110...230 VAC, max. 0.4A/110V | 110...230 VAC, max. 0.4A/110V |
Front Display & Front buttons | no | yes |
Status LED's & beeper | yes | yes |
Power monitoring inputs | 1 phase | 3 phases |
Switched outputs | 4 | 16 |
Digital Outputs, 1,5A@230VAC-2A@30VDC | 4 | 4 |
Digital Inputs, voltage free / Alarm Input | 8 / - | 8 / 4 |
Temperature / Humidity (digital) | 4 | 4 |
COM Interface front/rear (Terminal) | 1 / - | 1 / 1 |
AUX Interface rear (RS-232 D-9) | 1 | 1 |
Free programmable filters | 12 | 40 |
Users, max. | 12 | 100 |
DHCP Server | no | yes |
SNMP (Get, Set, Trap) | yes | yes |
Email function | no | yes |
Time server function | no | yes |
Syslog function | yes | yes |
UPS interface / support | no | yes |
MANUALS
| Name | Date | Size |
|---|---|---|
| German Manual for Rack Monitoring System Advanced | 2007-05-15 | 2.10MB |
| English Manual for Rack Monitoring System Advanced | 2007-05-15 | 2.07MB |